    ZW32-12F series outdoor Intelligent Vacuum Circuit Breaker is the outdoor distribution equipment of rated voltage 12 kV, three-phase AC 50/60HZ. This VCB is mainly used in load current, overload current and short circuit current of power distribution lines opening and closing of electric power system.designed to comply with the national standard GB1984 and IEC standards.
  • Category:
    Outdoor High Voltage Vacuum Circuit Breaker
  • Browse number:
    68
  • Release time:
    2024-09-21 14:58:37
  • Share:
  • INQUIRY

Description

Basic attributes: three-phase AC 50Hz, rated voltage 12kV, designed to comply with the national standard GB1984 and IEC standards. Core functions: load current, overload current, and short-circuit current can be divided and combined; Support automatic reclosing (multiple disconnections and rapid reclosing), suitable for protection and control of power distribution systems. Application scenarios: Outdoor distribution systems such as substations, industrial and mining enterprises, rural power grids, power plants, etc., especially suitable for frequent operating places.


Main functional features

1. Intelligent control function: This circuit breaker has functions such as local switch status control, three-stage overcurrent protection, and triple automatic reclosing. In addition, it also has RS-485 communication interface to achieve telemetry, remote adjustment, remote control, remote communication and other functions, which is suitable for various scales of automated distribution systems.


2. Permanent magnet operating mechanism: This circuit breaker adopts the most advanced permanent magnet operating mechanism currently available. The components of the mechanism are not worn, and its mechanical life can reach 30000 times, which is three times that of ordinary spring mechanisms. Due to the 70% reduction in the number of mechanical parts of permanent magnet mechanisms compared to spring mechanisms, the reliability of switches has been significantly improved.


3. Fully sealed structural design: The vacuum arc extinguishing chamber, operating mechanism, and connecting rod of this circuit breaker are fully sealed inside the circuit breaker base, solving the problem of corrosion of circuit breaker parts caused by condensation. The product can achieve maintenance free operation for 10 years.


4. Miniaturization structure: The circuit breaker adopts a new type of composite solid insulation material, which organically combines the vacuum arc extinguishing chamber, main electrical circuit, insulation support, etc. into an integrated solid sealed pole, completely solving the contradiction between miniaturization of the vacuum arc extinguishing chamber and meeting the requirements of external insulation. The entire product design is advanced and reasonable, with a compact structure, no condensation inside, and no rust on the mechanism.


Environment  condition

- Ambient temperature: max +40℃ min -40℃

- Altitude: ≤ 2000m

- Wind pressure: ≤ 700Pa (equals to wind speed 34m/s)

- Relative humidity: daily average relative humidity: ≤ 95%; monthly average relative humidity ≤ 90% - Air contamination degree: IV degree

- Earthquake intensity: ≤ 8 degree

- Not be contaminated by corrosive or flammable gas

- No frequent violent vibration or explosive place


Technical  Data

1Rated VoltageKV12
2Rated frequency HZ50
3Rated currentA630
4Rated short circuit breaking currentKA20, 25
5Rated peak withstand current (peak value)KA50, 63
6Rated short-time withstand currentKA20, 25
7Rated short circuit closing current (peak value)KA50, 63
8Mechanical lifeTimes10000
9Rated short circuit breaking current timesTimes30
10Power frequency withstand voltage(1min): (wet)(dry) same, earth / fractureKV42/48
11Lightning impulse withstand voltage (peak value) same, earth / fractureKV75/85
12Secondary circuit 1min power frequency withstand voltageKV2
13Rated operating voltage and rated voltage of auxiliary loopVAC220, 110 DC220, 110
14Rated current of over-current tripperA5
15Rated short-circuit durations4
16Contact open distance  mm9 ±1
17Contact Over-travelmm2.5±0.5
18Average opening speed  m/s1.1±0.2
19Average closing speed  m/s0.6±0.2
20Three-pole simultaneity          ms≤5
21Three-pole simultaneity (assembled with isolator)      ms≤2
22Distance of charged body and relative air  mm≤2
23Loop DC resistance per phases μΩ≤80
 (with isolator≤150)


Outline & Mounting Dimensions


Comment

(0)
*Captcha:

ONLINE MESSAGE

*Subject:
*E-mail:
Phone:
Address:
*Captcha:

RELATED PRODUCTS

Follow us:

Oil&Gas exploited

Automotive Manufacturing

Transportation & Dlistrlbutlon

Manufacture

Industrial Construction

Green Energy

About US

Contact US

The news

Terms & conditions

Case Studies

Site map

Copyright ? 2024  All Rights Reserved

Back to top